Del Rio EDC | Data Center Feasibility Platform

Val Verde County, TX • P&Z & Utility Interconnect Engine Active
Active Scenario
100 MW
Est. Capital Investment
$500M
Aquifer Preservation
97.2%
10-Yr Net Del Rio Tax Roll
$41.1M
▾ GIS & Zone Layers
Highlighted Jurisdictions & Zones
Laughlin AFB AICUZ Bufferℹ
Del Rio City Limitsℹ
P&Z I-1 & I-2 Industrial Zoningℹ
SFDRCISD Zoneℹ
Val Verde County Boundaryℹ
Infrastructure Corridors
Candidate Parcels (I-1/I-2ℹ / ETJℹ)
AEP 138 kV Transmission Grid (HIFLD Official)ℹ
AEP 138 kV Interconnect Substations
Fiber Corridors (US-90 / Spur 239)ℹ
Telco Meet-Me / Carrier PoPsℹ
San Felipe Springs (Protected)ℹ
Del Rio WWTP Effluent Plantℹ
Daily Potable Municipal Draw
12,400 gal
Drawn from Del Rio city potable water
Daily Recaptured / Effluentℹ
348,000 gal
Del Rio WWTP tertiary effluent + condensate
Annual Aquifer Preserved
128.5M gal
Protects San Felipe Springsℹ
Del Rio Water SLA Status
COMPLIANT
Operating WUEℹ: 0.12 L/kWhℹ (Ceiling: 0.20)

🎛️ Water Recapture Simulator

Model cooling technologies and municipal effluent integration

Data Center IT Load (MW) 100 MW
Del Rio WWTP Effluentℹ Substitution % 60%
Replaces potable water with tertiary-treated reclaimed purple-pipe water from Del Rio WWTP (Capacity: 4.5 MGD).
HVAC Condensate Harvestingℹ
Reclaims atmospheric humidity runoff from cooling coils (~18,000 gal/day).

📊 Cooling Water Impact Benchmark

Gallons / Day Comparison
🏭
Del Rio WWTPℹ
210k gal/d
Reclaimed Supply
🔄
Recaptured Loopℹ
95%+
Recirculated
🏞️
San Felipe Springsℹ
0.01%
Net Aquifer Draw

🚰 Reclaimed Water Pipeline Capital Expenditure (CapEx) Schedule

Del Rio WWTP tertiary effluent purple-pipe extension routes, booster stations & TCEQ Chapter 210 permitting

70% Developer / 30% EDC-City Match
Candidate Parcel Corridor WWTP Distance Trenching & Pipe ($185/LF) Booster Pump Lifts TCEQ 210 Permitting Total Pipeline CapEx Developer Share (70%) EDC / City Match (30%)
Site A: Del Rio Industrial Park (Farley Ln) 3.4 km (11,155 LF) $2.06M 1 Station ($450k) $85k $2.99M $2.09M $897k
Site B: East US-90 Logistics Corridor 9.2 km (30,184 LF) $5.58M 2 Stations ($900k) $85k $7.55M $5.29M $2.27M
Site C: North US-277 Energy Hub 10.9 km (35,761 LF) $6.62M 2 Stations ($900k) $85k $8.74M $6.12M $2.62M
Site D: Ports-to-Plains Gateway (Spur 239) 3.1 km (10,171 LF) $1.88M 1 Station ($450k) $85k $2.78M $1.95M $834k
*Note: Estimates reflect 12" C900 PVC non-potable purple pipe in public ROW, includes 15% engineering, construction management, and contingency. Sourced from Del Rio WWTP (Capacity: 4.5 MGD).
Configured IT Demand
100 MW
Peak operational electrical demand
Total Facility Load (PUEℹ 1.15)
115 MW
Includes cooling & power transformation overhead
Annual ERCOTℹ Consumption
1,007 GWh
Estimated annual energy throughput
Substation Tie-In Estimate
$8.5M - $14M
AEP 138 kVℹ redundant interconnect

⚡ Electric Load & Transmission Parameters

AEP Texasℹ & ERCOT Regionℹ
Campus Electrical Capacity 100 MW
Behind-The-Meter Solar PV Co-Location 40 MW Solar
Val Verde County boasts prime DNI solar irradiance (~5.5 kWh/m²/day). Offsets summer peak ERCOT grid pricing.
Battery Energy Storage System (BESS)ℹ 100 MWh
Provides 1 to 2 hours of seamless ride-through and peak shaving, enhancing AEP Texas local substation resilience.

📋 Interconnection Steps & Milestones

Fast-Track Queue
1. ERCOT Interconnection Studyℹ (Section 22 Agreement)
Estimated timeline: 6–9 months. Submittal of Large Load (LL) interconnection request with AEP Texas under ERCOT rules.
2. Dedicated On-Site Substation Engineering
Dual 138/34.5 kV or 138/13.8 kV main power transformers (MPTs) with N+1 redundancy and dual bus configuration.
3. ERCOT Demand Response & Ancillary Services
Enrollment in Controllable Load Resource (CLR) / Responsive Reserve Service (RRS), creating revenue streams during grid peaks.
4. Laughlin AFB AICUZℹ & Flight Safety Review
FAA 7460-1 clearance for substation dead-end towers and verification of zero EMI interference with Laughlin training radar.

⏳ ERCOT Large Load Interconnection & Substation MPT Procurement

PGRR115 energization risk bands and national transformer supply chain tracking

Formal ERCOT Queue (≥75 MW)
Fast-Track Interconnection Band (<75 MW) 12–18 Months
Expedited Transmission Service Provider (TSP - AEP Texas) engineering study utilizing available terminal bay capacity on existing 138 kV line corridors with fast-tracked ERCOT screening (does not trigger full LLIS).
Formal ERCOT Large Load Queue Band (≥75 MW) 24–36 Months
Formal Large Load Interconnection Study (LLIS) governed under ERCOT PGRR115 / Section 9.7 (Steady-State, Dynamic stability, and Short-Circuit modeling), ERCOT Board endorsement, and complete greenfield dedicated substation buildout.
⚠️ High-Voltage Step-Down Substation Transformer (MPT) Lead Time Warningℹ
National lead times for 138 kV Step-Down Main Power Transformers (MPTs) are currently 100–140+ weeks (2.0–3.0 years) across all major OEMs (Hitachi Energy, Siemens Energy, Prolec GE, WEG) and can extend to 3–4 years for bespoke large units. Note: Load facilities require Step-Down MPTs (138 kV to 34.5/13.8 kV), not Generator Step-Up (GSU) units. Mitigation: Del Rio EDC recommends early equipment slot reservation upon Phase 1 MOU signing.

🛡️ Community Impact & Public Safety Guardrails

Acoustic decibel (dBA) attenuation and NFPA 855 BESS battery protocols

NFPA 855 / UL 9540A
Boundary Acoustic Attenuationℹ ≤ 48 dBA Day / ≤ 42 dBA Night
Unmitigated chiller/generator noise (90 dBA source at 10 ft) attenuated via 500-foot setback and 16-foot masonry sound barriers. +17 dBA compliance margin below City of Del Rio industrial noise threshold (65 dBA).
BESS Safety Standards (NFPA 855 & UL 9540A)ℹ 100 MWh LiFePO4
  • Lithium Iron Phosphate (LiFePO4 / LFP): High thermal runaway resistance (>270°C).
  • Continuous Multi-Gas Detection: Off-gas sensors monitor H2 and CO before runaway can initiate.
  • Deflagration Relief & Water Deluge: NFPA 68 rooftop explosion venting and dry-pipe deluge curtain with 5" Storz Del Rio Fire Dept hookups.
  • 10-Ft Enclosure Separation: Buffers between BESS units prevent cascading thermal propagation.

🎯 Del Rio EDC Target Partner Profiles

Data center operators and hyperscalers profiled by load, cooling tech, and Del Rio value fit

🏛️ Tax Abatement & Municipal Clawback Sandbox

15-year jurisdictional revenue modeling (City, County, SFDRCISD, Hospital) & breach penalty simulator

10-Year City of Del Rio Net Tax
$10.3M
New commercial tax revenue to Del Rio general fund
10-Year SFDRCISD School Net Tax
$22.0M
Includes Chapter 403 (JETI Act)ℹ M&O model
Total 10-Yr All-Entity Net Revenue
$41.1M
City, County & SFDRCISD School District
15-Year Projected Total Impact
$72.2M
Full tax base realized post-abatement period

🏛️ Chapter 380ℹ / Chapter 381ℹ Incentive Architecture

Configure ad valoremℹ abatements and JETI parameters

Total Capital Expenditure (CapEx) $500M
Servers & power gear (~70% BPPℹ) + Building improvements & land (~30% Real Property).
City Chapter 380ℹ Abatement % 65%
Val Verde County Chapter 381ℹ Abatement % 60%
Abatement Term (Years) 10 Years
Texas Chapter 403 (JETI Act)ℹ School Abatement
Statutory 10-year limit: 50% M&O valuation limitation for SFDRCISD.

🛡️ Municipal Clawback Protectionℹ Stress-Tester

Configure agreement hurdle targets and simulate breach clawbacks

📋 Negotiated Agreement Hurdles (Targets) Chapter 380 Statutory Terms
Target Phase 1 CapEx Hurdle $150M
Target Contractual WUEℹ Ceiling (L/kWhℹ) 0.22 L/kWh
Negotiated municipal cooling SLA protecting local aquifers (single source of truth: ≤ 0.22 L/kWh).
Target Local Employment Floor 40 FTEs
⚠️ STRESS TEST SCENARIO: Developer Default & Clawback Mechanism Activation
Simulated performance audit demonstrating contractual default protections, municipal tax rebate clawbacks, and statutory damages under breach conditions.
Actual Developer CapEx Delivered ($M) $110M (Target: $150M)
Actual Operating WUEℹ (L/kWhℹ) 0.29 L/kWh (Ceiling: 0.22)
Actual Local High-Wage FTEs Employed 21 FTEs (Target: 40)

📈 15-Year Projected Tax Revenues by Jurisdictional Entity

Reflects 4-Year BPPℹ Server Refresh Cycles
Year Total Valuation City Gross City Abated (Ch. 380ℹ) City Net Revenue County Net Revenue SFDRCISD Net Revenue Total Combined Net

🛡️ 5.2 STRESS TEST SCENARIO: Developer Default & Municipal Clawback Enforcement Schedule

Contractual performance hurdles vs simulated audit and enforceable statutory financial recapture ledger

Enforceable Statutory Remedy
Stress Test Scenario Audit Protocol:

Evaluates contractual non-performance ($110M / $200M CapEx delivered, 0.29 WUE, 21 FTEs) directly beneath standard accretion projections to demonstrate enforceable statutory clawbacks, liquidated damages, and legal remedies recapturing public abatements under Chapter 380/381 performance agreements.

Negotiated Hurdle / Covenant Contractual Target (Ceiling/Floor) Simulated Performance Audit Audit Status

Simulated Default: Municipal Financial Recapture Breakdown

Jurisdiction / Recapture Entity Statutory Remedy / Mechanism Financial Clawback Amount

📄 Del Rio EDC Executive Feasibility Study Brief

Official policy recommendation document prepared for City Council & EDC Board